Item Specs:
Features
- Control ignition sequence and gas control operation.
- Generate high voltage potential for main burner ignition.
- Lockout after one trial for ignition if main burner fails to ignite.
- Reset from thermostat after lockout.
- Use modules (except S87C) with any combination gas control designed for direct spark applications and rated 2.0A or less.
Specifications
- Description: Provide electronic control of direct spark ignition systems used on gas fired furnaces, boilers, and other heating appliances.
- Ignition System Type: Direct Spark Ignition
- Ignition Sequence: Single trial for main burner ignition (then shut down and lockout)
- Typical Gas Control: VR8205, VR8305
- Type of Gas: Natural or LP
- Ignition Source: Internal high voltage spark generator
- Prepurge: None
- Ignition Trials To Lockout: 1
- Typical Ignition Hardware: Q347A
- Dimensions: 5 1/4 in. high x 4 1/16 in. wide x 1 15/16 in. long
- Electrical Ratings: 24 Vac
- Frequency: 60 Hz
- Max Ambient Temperature: -40 F to +175 F
- Includes: Alarm terminal
- Flame Failure Response Time: 0.8 sec. @ 5.0 microamp
Condition: | New: A brand-new, unused, unopened, undamaged item in its original packaging ... | Brand: | Honeywell |
MPN: | S87C1006 |
Shipping & Delivery |
We ship Worldwide. Get shipping and tax estimate by adding the item into your shopping cart. Estimated delivery time will depend on shipping service selected and receipt of cleared payment. Delivery times may vary |
Payment | We accept paypal and all major credit cards |
Returns | 30 Days Money Back Guarantee: Get the item you ordered or get your money back. Non Defective :Within 30 days after receiving the item, buyer needs to Contact SPW Industrial for return. Item will be refunded or exchanged. After 30 days there will be a restocking fee, learn more |
Warranty | SPW Industrial warrants this product to be free of defects in workmanship and material under normal use and conditions for period of one year from the date of original purchase |